Electrical · Impact ratings
IK rating chart in joules.
Turn an IK code into impact joules, or a joule requirement into the lowest IK code that meets it.
Short answer: IK00 to IK11 are test impact energies: IK06 is 1 J, IK08 is 5 J, IK09 is 10 J, IK10 is 20 J and IK11 is 50 J. IK covers impact only, not dust or water.
Result
Enter a code such as IK08 and press Decode.
Enter a joule value, such as 10, and press Find IK code.
What an IK code is
The IK code rates how much mechanical impact an enclosure shrugs off. It is the letters IK and a two-digit number, from 00 to 11. Each number stands for a test impact energy in joules, so the code is really a short way of writing how hard a blow the enclosure was tested against. It is defined by IEC 62262. Its scope, quoted from the IEC preview of the standard, is the degrees of protection against external mechanical impacts for equipment whose rated voltage is not greater than 72.5 kV, and it applies only where the product standard for the equipment sets a degree of protection against impacts.
That second condition matters. IK is not a free-floating badge. It exists to be called up by a product standard or a specification, which then says which level the enclosure must meet.
The chart
| IK code | Test impact energy (joules) |
|---|---|
| IK00 | Not protected according to the standard |
| IK01 | 0.14 J |
| IK02 | 0.2 J |
| IK03 | 0.35 J |
| IK04 | 0.5 J |
| IK05 | 0.7 J |
| IK06 | 1 J |
| IK07 | 2 J |
| IK08 | 5 J |
| IK09 | 10 J |
| IK10 | 20 J |
| IK11 | 50 J (added by the 2021 amendment) |
These joule values are the same in every chart we could read in full: Wikipedia’s IK code article, a lighting manufacturer’s guide and a second lighting distributor’s table all agree, and Designplan prints the top four from the BS EN 62262 table. The IEC preview confirms the numeral range: the original standard’s numerals ran 00 to 10, and the 2021 amendment extends them to 11.
Why this page does not print hammer masses or drop heights
Most IK charts add two more columns, the mass of the striking hammer and the height it falls from. We left them out on purpose, because the charts disagree with each other. For IK07, one manufacturer prints a 0.5 kg hammer dropped from 40 cm, while a distributor’s table prints 500 g from 20 cm. For IK08, one source gives 1.7 kg from 30 cm, Designplan gives 1.75 kg at 300 mm, and the distributor’s table gives 5 kg from 10 cm. For IK10, one chart says 5 kg from 40 cm and another says 10 kg from 40 cm. Those cannot all be right, and the authoritative figures sit in the paid standard, whose table the free preview does not include. The energy column is the one that is consistent, and it is the one that defines the rating.
Reading joules as a drop
Energy in joules is mass times gravity times height, so a rough feel is possible. These are hypothetical illustrations of the energy only, not the actual test, which uses a calibrated hammer: a 1 kg object falling about 10 cm carries roughly 1 J, which is the IK06 energy. Dropped from about 51 cm it carries roughly 5 J, the IK08 energy. Dropped from about 2 m it carries roughly 20 J, the IK10 energy. The point of the arithmetic is scale: moving up three codes near the top of the chart is not a small step. Each of IK08, IK09 and IK10 doubles the energy of the one before it.
Worked example
Suppose a specification for a wall-mounted luminaire in a school gym asks for impact resistance of at least 10 J. Hypothetically, you are comparing three datasheets that read IK07, IK09 and IK10. IK07 is 2 J, below the requirement. IK09 is exactly 10 J, which meets a minimum of 10 J. IK10 is 20 J, which exceeds it. Type 10 into the second tool above and it returns IK09, the lowest level whose test energy is at least that value. Whether 10 J is the right number for a gym is a question for the specifier or the product standard, not for this page.
Common mistakes
- Reading IK as a pass mark for everything. An IK10 rating is a single standard test energy, 20 J. It is not a promise that the enclosure is unbreakable, and the code says nothing about other loads or repeated blows.
- Confusing IK with IP. IP rates dust and water, IK rates impact. A fixture can be IP66 and IK03. Our IP rating chart covers the other one.
- Assuming codes above IK11 exist. The standard allocates none. Designplan states that BS EN 62262 does not allocate codes above IK11, and it publishes IK12 to IK20 as its own extension. Treat those as vendor claims.
- Using an old datasheet. Anything written before the 2021 amendment stops at IK10.
- Quoting hammer masses from a random chart. As shown above, they conflict.
Who this is for
Facilities managers, lighting and security-camera buyers, panel builders and anyone reading a spec sheet that mentions IK. If you are checking a datasheet against a requirement written in joules, the second tool turns the joule figure into the code you should look for.
What this does not cover
- It does not tell you which IK level a given installation needs. That comes from the product standard, the code of practice or the risk assessment.
- It does not print hammer mass, drop height or the test procedure; those are in the paid standard and the public charts conflict.
- It does not verify that a product was tested to IEC 62262 or by whom.
- It does not rate dust, water or corrosion.
Frequently asked questions
What is IK10 in joules?
IK10 corresponds to a test impact energy of 20 joules. The scale above it, IK11 at 50 joules, was added by the 2021 amendment to IEC 62262.
What does IK08 mean?
IK08 means the enclosure was tested against an impact energy of 5 joules. It is the energy of the test blow, not a claim about any particular object.
What is the difference between IK and IP ratings?
IK rates resistance to mechanical impact in joules. IP rates protection against solid objects, dust and water. A product can carry both, and one says nothing about the other.
Is there an IK11 or higher?
IK11 (50 J) exists since the 2021 amendment. The standard allocates no codes above IK11; ratings such as IK12 to IK20 are vendor extensions, not part of IEC 62262.
What does IK00 mean?
IK00 means not protected according to the standard. It is the bottom of the scale, with no impact energy attached.
Which IK rating do I need?
It depends on where the enclosure is mounted and what the product standard or specification requires. This page converts a joule requirement into the lowest matching code but does not set the requirement.
Why do IK charts show different hammer weights?
Public charts disagree on hammer mass and drop height for several levels, for example IK07 and IK08. The energy values agree, so this page publishes only those.
Does a higher IK rating mean an enclosure cannot break?
No. It means the enclosure was tested at that impact energy under the standard’s conditions. Other loads, repeated blows and sharp objects are outside the rating.
Sources
Retrieved
- Wikipedia: IK code (IK00 to IK11 joules, 2021 amendment)
- i-valo: IK rating explained (joules; IK covers impact, IP covers dust and water)
- TRT Lighting: IP and IK ratings (joules, and a hammer table that conflicts with others)
- Designplan: IK ratings (BS EN 62262 table IK08 to IK11; no codes above IK11)
- IEC 62262 Edition 1.1 (2021-09) preview, via VDE Verlag (title, scope, numerals 00 to 11)
- BSI: BS EN 62262:2002+A1:2021 catalogue entry (title and date only)
Reference only — not a certification check
This page lists the impact energies behind IK codes and converts between them. It does not verify that a product was tested and it does not decide which level an installation needs. For compliance work use IEC 62262 and the relevant product standard. TNAADO is not affiliated with IEC, BSI or any manufacturer named.