Electrical · Building wire
THHN vs THWN-2 vs XHHW: wire marking decoder.
Type a marking such as THHN/THWN-2. Each letter is explained and the dry and wet ratings are combined.
Short answer: THHN is 90 C dry only. THWN is 75 C wet and dry. THWN-2 is 90 C wet and dry, and the -2 is that wet rating. XHHW is 90 C dry and 75 C wet, XHHW-2 is 90 C both. A wire with two markings carries both ratings.
Result
Enter a marking such as THHN/THWN-2 and press Decode.
Reading the letters
The marking printed on building wire is a compact description of the insulation, written as letters. They are not decorative. Each letter adds one fact, and the dash-2 suffix changes the wet rating. Read from left to right they mean:
| Letter | Meaning |
|---|---|
| T | Thermoplastic insulation, which is PVC. |
| X | Cross-linked polyethylene (XLPE) insulation, a thermoset. |
| H | Heat-resistant, 75 C. |
| HH | High heat: 90 C in dry locations. |
| W | Water-resistant, rated for wet locations. |
| N | A nylon outer jacket over the insulation. |
| -2 | Rated 90 C in both wet and dry locations. It is a wet rating, not a version number. |
The five markings this decoder covers
| Marking | Insulation | Dry | Wet | Where |
|---|---|---|---|---|
| THHN | PVC with nylon jacket | 90 C | Not wet-rated | Dry and damp locations |
| THWN | PVC with nylon jacket | 75 C | 75 C | Dry, damp and wet locations |
| THWN-2 | PVC with nylon jacket | 90 C | 90 C | Dry, damp and wet locations |
| XHHW | XLPE | 90 C | 75 C | Dry, damp and wet locations |
| XHHW-2 | XLPE | 90 C | 90 C | Dry, damp and wet locations |
Wikipedia’s description of these types and a cable-type guide from ToolGrit agree on every row for THHN, THWN, THWN-2 and XHHW-2. For plain XHHW, ToolGrit gives 90 C dry and 75 C wet, and Wikipedia says the original XHHW was equivalent to dual-rated THHN/THWN insulation, which is the same pair of figures. These are the insulation temperature ratings. They are not ampacity: a conductor’s allowable current depends on the code tables and the terminals it connects to, and this tool does not calculate it.
Why one wire carries two markings
Most building wire is printed with more than one designation, such as THHN/THWN-2. That is one conductor meeting both specifications, so it carries both ratings at once. A manufacturer specification sheet for THHN/THWN-2 wire lists the ratings it covers: THHN for dry locations to 90 C, THWN-2 for wet or dry locations to 90 C, and THWN for wet locations to 75 C. Its marking line reads THHN or THWN-2 600V 90 C DRY OR WET. The decoder follows that logic: type both markings and it reports the highest dry figure and the highest wet figure that apply together.
The same sheet carries a warning worth knowing. That product is marked THHN in all sizes, but THWN-2 only in sizes 8 AWG and larger, and THWN rather than THWN-2 in sizes 14, 12 and 10 AWG. In other words, in the small sizes common in houses, a wire sold as THHN/THWN may carry the 75 C wet rating rather than 90 C. The only reliable answer is the print on the actual jacket.
A conflict between sources, and which way we went
One distributor guide states that THHN/THWN-2 is rated 90 C dry and 75 C wet. That conflicts with Wikipedia, with ToolGrit and with the same distributor’s own product specification sheet, which all give 90 C wet for THWN-2. We followed the specification sheet and the two independent references, and left the 75 C figure out. If a datasheet in front of you disagrees with this page, trust the datasheet for that product, not this table.
Worked example
These are hypothetical situations. Case one: a conductor printed THHN only. The decoder returns 90 C dry and no wet rating, so it does not carry a wet-location claim, and you would look for a marking with a W before using it where water can reach. Case two: a coil printed THHN/THWN-2. The decoder returns 90 C dry and 90 C wet, because the THWN-2 half supplies the wet rating. Case three: a #12 wire printed THHN/THWN. The highest dry figure is 90 C from the THHN half, and the wet figure is 75 C from the THWN half. Whether any of these is acceptable for a given raceway is a code question for you or your electrician, not a marking question.
Common mistakes
- Reading THHN as "wet-rated because it is nylon-coated". The nylon is the N. The W is what signals wet.
- Assuming -2 means a newer revision. It means 90 C wet and dry.
- Treating the insulation temperature as the wire’s current capacity.
- Believing every THHN wire is also THWN-2. Some sizes are not.
- Expecting this to decode cable assemblies. NM-B and similar types are names for sheathed cables, not insulation codes of this kind; the NM stands for nonmetallic sheathing.
Who this is for
DIYers and apprentices standing at a spool wondering what is printed on it, buyers comparing two listings, and anyone writing a materials list who wants the wet versus dry question answered quickly. If you are sizing conduit for the wire you identify, use the conduit fill calculator.
What this does not cover
- Types beyond the five listed, such as the older rubber types and appliance-wiring marks; it says so rather than guessing.
- Ampacity, voltage drop and derating.
- Sheathed cables such as NM-B and UF.
- Whether a wire is acceptable for a location. That is set by the electrical code and the local authority.
Frequently asked questions
What is the difference between THHN and THWN-2?
Both are PVC insulation with a nylon jacket rated 90 C dry. THWN-2 adds the water-resistant W and the -2, so it is also rated 90 C in wet locations. THHN alone has no wet rating.
Can THHN wire be used in wet locations?
Plain THHN is rated for dry and damp locations only. Wire marked THHN/THWN-2 carries the wet rating through the THWN-2 half, so look for that marking on the jacket.
What does the -2 mean on THWN-2 and XHHW-2?
It means the conductor is rated 90 C in both wet and dry locations. It is a wet rating, not a version number.
What do the letters T, H, W and N mean?
T is thermoplastic (PVC) insulation, H is heat-resistant at 75 C, HH is high heat at 90 C dry, W is water-resistant and N is a nylon jacket. X stands for cross-linked polyethylene.
What is XHHW wire?
XHHW is wire with cross-linked polyethylene (XLPE) insulation, a thermoset. XHHW is rated 90 C dry and 75 C wet, and XHHW-2 is rated 90 C wet and dry.
Why does my wire have two markings, like THHN/THWN-2?
One conductor can meet both specifications and carries both ratings. The highest dry figure and the highest wet figure apply together.
Is NM-B the same kind of marking?
No. NM-B names a nonmetallic-sheathed cable, a jacketed assembly, not an insulation code like these. This decoder does not cover it.
Does the temperature rating tell me how many amps the wire can carry?
No. The temperature rating is the insulation limit. Allowable current depends on code tables, wire size, conditions and terminal ratings, which this page does not calculate.
Sources
Retrieved
- Wikipedia: Electrical wiring in the United States (THHN, THWN, THWN-2, XHHW-2 expansions and ratings)
- ToolGrit: cable type decoder guide (letter meanings, dry and wet table, -2 is a wet rating)
- IEWC: THHN/THWN-2 600V product specification sheet (ratings, marking line, sizes marked THWN-2)
- IEWC: THHN vs THWN vs Romex vs XHHW technical guide (T, X, HH, W, N letter meanings; conflicts with the sheet on THWN-2 wet rating)
Reference only — follow the printed marking and the code
This page explains what building-wire markings mean in general. The authority for any conductor is the marking on its jacket, the manufacturer’s datasheet and the electrical code in force where you work. It does not size circuits or approve a wire for a location. TNAADO is not affiliated with any company named.