Home energy · off-grid

Off-grid solar system size calculator.

Daily kWh in, array kW, panel count, battery kWh and inverter watts out. Size for the worst month, not the average.

Worst-month sizingEditable lossesChecked 15 October 2026

Advertisement

Inputs

Add up your loads with the off-grid load calculator.
Use the lowest month you must run through, not the annual average.
NREL PVWatts default is 14%.
Read it from the inverter datasheet.
Placeholder; read it from the battery datasheet.
DOE says off-grid battery banks are typically sized for 1 to 3 days.
Battery University: makers often rate at 80% DoD. Use your maker's figure.
A rule of thumb, not a published standard.

System size

Enter your numbers.

How do you size an off-grid solar system?

Start with the energy you use per day, then work backwards through each loss. Array kW = daily kWh / (peak sun hours x (1 - system losses) x inverter efficiency x battery efficiency). Peak sun hours are the hours per day at 1 kW/m² that would give the same energy as the day's real sunlight, so use the lowest month you need to cover. Battery kWh = daily kWh x days of autonomy / usable depth of discharge / inverter efficiency. DOE notes off-grid battery banks are typically sized for 1 to 3 days.

Worked example. 5 kWh per day, 2.5 peak sun hours in the worst month, 14% losses, 95% inverter and 90% battery efficiency: 5 / (2.5 x 0.86 x 0.95 x 0.90) = 2.72 kW, which is 7 panels of 400 W (2.8 kW). Two days of autonomy at 80% depth of discharge: 5 x 2 / 0.8 / 0.95 = 13.2 kWh of battery.

Frequently asked questions

How many solar panels do I need to go off-grid?

Divide the array kW from this tool by your panel wattage and round up. With 5 kWh per day, 2.5 peak sun hours in the worst month and the default losses it is about 2.7 kW, or 7 panels of 400 W.

Which peak sun hours should I use off-grid?

The lowest month you have to run through without a backup generator. Using the annual average undersizes the array for winter.

How many days of battery autonomy do I need?

DOE's Small Wind Guidebook says off-grid battery banks are typically sized for 1 to 3 days of load. Your answer depends on how long poor weather lasts and whether you have a generator.

Does this include a generator or wind?

No. It sizes a solar-only system. A generator or wind turbine reduces the array and battery you need; see the wind tools in the related list.

Sources

Checked

The 14% loss figure is the NREL PVWatts default and the 1 to 3 day autonomy range is from DOE. Inverter and battery efficiency, inverter headroom and the example loads are placeholders you should replace with datasheet values. Runs entirely in your browser. Nothing you type is sent or stored.

Scope

Planning estimate only. Off-grid systems involve high DC current and stored energy; have the design reviewed and installed to your local electrical code by a qualified person.