Home energy · EV charging

What breaker does a charger need?

Charger amps and volts in, kW and minimum circuit protection out. A planning aid for the conversation with your electrician, not an installation design.

Advertisement

Inputs

Starting values are illustrative, not current prices or specifications. Replace each with your own.

The charger's rated output current, from its nameplate or settings.
240 V is typical for a home Level 2 circuit in North America.
Enter the breaker you have to see the largest continuous charger current it can serve.

Result

Answer

A charger rated at 32 A on 240 V delivers 7.68 kW and needs circuit protection of at least 32 × 1.25 = 40 A, because EV charging counts as a continuous load. Wire size, panel capacity and local code still decide what can be installed.

Worked example

A 32 A charger on 240 V is 32 × 240 ÷ 1,000 = 7.68 kW. The circuit protection must be at least 32 × 1.25 = 40 A, so a 40 A breaker is the smallest common size. A 48 A charger needs 60 A at minimum (11.52 kW). A 30 A charger (7.2 kW) needs 37.5 A, so the next size is 40 A, which matches the dedicated 40 A circuit AFDC describes for 7.2 kW home units.

Formulas and notes

Electrical safety: this page is not electrical advice. Charger circuits must be designed and installed by a licensed electrician to your local code. Do not use extension cords or adapters for sustained EV charging.

Planning estimate only, not professional advice. Sources, checked 2026-10-08: EC&M, NEC Requirements for EV Equipment (Nov. 9, 2023) · U.S. DOE Alternative Fuels Data Center, Electric Vehicle Charging Stations

FAQ

What size breaker do I need for a 48 amp EV charger?

At least 60 A. EV charging is a continuous load (EC&M, NEC 625.42), and continuous loads are conventionally sized at 125 percent of the load: 48 × 1.25 = 60 A. The AFDC 30 A to 40 A example is consistent with this.

Why is the breaker bigger than the charger amps?

Because the charger runs for hours at a steady load, protection and conductors are sized with a 25 percent margin so the circuit does not run at its limit for the whole charge.

Can I install an EV charger circuit myself?

Have a licensed electrician do the work and pull any permit your jurisdiction requires. This calculator is a planning aid and does not select wire, check your panel or know your local code.

How many kW is a 40 amp EV charger?

On 240 V, 40 A is 9.6 kW. Its circuit protection would need to be at least 50 A.

Does this apply in Canada?

The 125 percent continuous-load convention used here follows U.S. National Electrical Code practice. Canada uses the Canadian Electrical Code and provincial rules, which can differ, so confirm with a licensed Canadian electrician.