Construction Calculators
Voltage Drop & Wire Size Calculator
Enter voltage, amps, one-way distance, metal and AWG to see the voltage drop in volts and percent, and the smallest wire gauge that stays under your limit. Works for 120/240 V AC, three phase and 12 V DC.
Inputs
Results
Fill the form and press Calculate.
How it works
Frequently asked questions
How do I calculate voltage drop?
For DC or single-phase AC, drop in volts = 2 x current x resistance per foot x one-way length. Three-phase uses 1.732 instead of 2. Divide by the source voltage for percent. This page does exactly that, using the resistance of the AWG you pick.
What wire gauge do I need for 30 amps?
Two separate checks apply. Ampacity (how much current the wire may carry) comes from the NEC; see 310.16 and 240.4(D) in your adopted edition, and ask a licensed electrician. Voltage drop depends on distance: enter 30 A, your voltage and your one-way length, and this tool shows the smallest AWG that stays under your percent limit. Use whichever size is larger.
Is 3% voltage drop a rule?
No. The informational notes to NEC 210.19(A) and 215.2(A) recommend sizing so branch-circuit drop is no more than 3% and feeder plus branch together no more than 5%. They are recommendations, though your local code, the equipment maker or the inspector may require more.
How does 12V DC (RV, solar, boat) differ?
The math is the same but the voltage is small, so the same volts lost is a much bigger percent. 3 V lost on 12 V is 25%. Marine and solar guidance often aims for 3% or less, so wire sizes grow quickly with distance. Select single phase / DC and enter 12 as the voltage.
Why does my result differ from another calculator?
Differences usually come from the resistance table used, the conductor temperature (hot wire has higher resistance; this tool lets you set it), whether round-trip length is used, and whether AC reactance is included. This tool is resistance-only and uses 10.371 ohm-cmil/ft for copper at 20 C.
Does this size wire for safety?
No. It checks voltage drop only. It does not check ampacity, breaker or fuse size, insulation, conduit fill, derating or terminals. Have a licensed electrician confirm any real installation.
Worked example: 30 A load, 100 ft run on 240 V
A single-phase copper circuit at 240 V carries 30 A over 100 ft one way at 75 °C. In 10 AWG copper, resistance is 1.215 ohms per 1,000 ft. Drop = 2 × 30 A × 1.215 × 0.1 = 7.29 V, which is 3.04% of 240 V and leaves 232.7 V at the load. That is just over the 3% branch-circuit recommendation. Stepping up to 8 AWG cuts the drop to 4.58 V (1.91%), so 8 AWG is the smallest size under a 3% target. Ampacity is a separate check this tool does not do.
Sources and method
Checked
Resistance only. AC reactance and power factor are ignored, which is small at branch-circuit sizes. Figures as of October 26, 2026.
- NFPA 70 (National Electrical Code): the 3% branch and 5% total figures come from informational notes to 210.19(A) and 215.2(A). They are recommendations, not requirements.
- Wire diameters follow ASTM B258; copper resistivity is 10.371 ohm-cmil/ft at 20 °C (100% IACS, ASTM B3/B193) and aluminum 17.0, corrected for temperature in the tool. No NEC table is reproduced.
Frequently asked questions
What voltage drop is acceptable?
The NEC informational notes recommend no more than 3% on a branch circuit and 5% for feeder plus branch combined. They are not mandatory, but equipment can misbehave when the drop is larger.
Why does the formula use twice the length?
On a single-phase or DC circuit the current flows out on one conductor and returns on another, so the resistance that matters is that of twice the one-way distance. Three-phase uses √3 instead.
Does this pick a wire size for code compliance?
No. It finds the smallest size that meets your drop target. Ampacity, terminations, conduit fill and local code can require a larger conductor.
Why does temperature change the result?
Conductor resistance rises with temperature, so the same wire drops more voltage when it runs hot. Enter the conductor temperature you expect.